Insulation Resistance Tester UCL2014

Usage

Insulation resistance tester is used to test the characteristics of insulation resistance value of insulating appliances and insulating materials under specified medium environment and specified voltage.

 

Feature

Use the micro-computer to control, menu operation, LCD display, stable performance, smart instrument.

Strong anti-interference capability.

7 voltage output taps: 50V, 100V, 250V, 500V, 1.0kV, 2.5kV, 5.0kV.

Can adjust the output high voltage continuously from zero.

Automatically measure R15, R60 and R600; calculate the absorption rate and polarization index and display the leakage current and absorbed capacitance.

Strong load capacity and the short-circuit current is about 5mA.

Measuring range 0-10TΩ and automatic range switch.

Display the test time at any time and the buzzer sounds every 15s.

If the test object is found to be live before test, live voltage and related prompts will be shown.

Be allowed to set the test time

Automatically measure the ambient temperature, humidity, test date and time.

Can store 60 days of test results.  

With RS232 interface

If no operations within 5 minutes, the device prompts you to shut down the computer.

Having all-round protection functions and high reliability.

 

Technical parameters

Rated test voltage

50V ~ 10.0KV

Upper limit

100GΩ ~ 10TΩ

Lower limit

0.1MΩ

Output voltage error

±5%

Short-circuit current

about 5mA

Accuracy level

5.0

Lower half range basic error

±( 5%·Rx + 1d )

Upper half range basic error

±( 10%·Rx + 2d )

HV display error

±( 5%·Ux + 1d )

Leakage current display range & error

0.1nA~9.9mA    5%

Absorbed capacitance display range & error

0.1pF~99μF    5%

Temperature measuring error

±0.5

Air humidity measuring error

±2%RH

Power

14.8V lithium cell

Battery charging time and duration

30days 10 times DAR per day & 5 times PI tests

Insulation resistance

> 500 MΩ (between test lines and cabinet)

Voltage withstand

AC10.0kV 50Hz 1min

Working temperature & humidity

0~ + 40℃   < 85%RH

Storage temperature & humidity

- 20~ + 50℃  < 90%RH

Dimension (mm)

270(L) ×240 (W) ×165(H)

Weight (kg)

4.5